Query
For a project, we are providing sub-meters for indoor and outdoor lighting - . Project has a separate sub-meter for outdoor lighting whereas for indoor areas there is a joint sub-meter for lighting and ceiling fan load (in classrooms).
Please confirm whether the above is acceptable.
Response
Yes, the joint meter for internal lighting and ceiling fan is acceptable. To support the same project team should submit electrical floor plan along with lighting and fan inventory highlighting the load distribution.